OpenPLC_v3/webserver/dnp3.cfg

62 lines
1.4 KiB
INI

# ----------------------------------------------------------------
# Configuration file for DNP3
#-----------------------------------------------------------------
# Use this file to fill out DNP3 settings for your Open PLC
# Uncomment settings as you want them
# Link Settings
#-----------------------------------------------------------------
# local address
local_address = 10
# master address allowed
remote_address = 1
# keep alive timeout
# time (s) or MAX
# keep_alive_timeout = MAX
# Parameters
#-----------------------------------------------------------------
# enable unsolicited reporting if master allows it
# True or False
enable_unsolicited = True
# how long (seconds) the outstation will allow a operate
# to follow a select
# select_timeout = 10
# max control commands for a single APDU
# max_controls_per_request = 16
# maximum fragment size the outstation will recieve
# default is the max value
# max_rx_frag_size = 2048
# maximum fragment size the outstation will send if
# it needs to fragment. Default is the max falue
# max_tx_frag_size = 2048
# size of the event buffer
event_buffer_size = 10
# number of values the outstation will report at once
# AKA database size
database_size = 10
#Timeout for solicited confirms
# in MS
# sol_confirm_timeout = 5000
#Timeout for unsolicited confirms (ms)
# unsol_conrfirm_timeout = 5000
#Timeout for unsolicited retries (ms)
# unsol_retry_timeout = 5000