OpenPLC_v3/webserver/lib/hysteresis_st.txt

22 lines
510 B
Plaintext
Executable File

(* Following taken directly from the IEC 61131.3 draft standard *)
(*
* An IEC 61131-3 IL and ST compiler.
*
* Based on the
* FINAL DRAFT - IEC 61131-3, 2nd Ed. (2001-12-10)
*
*)
FUNCTION_BLOCK HYSTERESIS
(* Boolean hysteresis on difference *)
(* of REAL inputs, XIN1 - XIN2 *)
VAR_INPUT XIN1, XIN2, EPS : REAL; END_VAR
VAR_OUTPUT Q : BOOL := 0; END_VAR
IF Q THEN IF XIN1 < (XIN2 - EPS) THEN Q := 0; END_IF ;
ELSIF XIN1 > (XIN2 + EPS) THEN Q := 1 ;
END_IF ;
END_FUNCTION_BLOCK