(* Following taken directly from the IEC 61131.3 draft standard *)
|
|
|
|
(*
|
|
* An IEC 61131-3 IL and ST compiler.
|
|
*
|
|
* Based on the
|
|
* FINAL DRAFT - IEC 61131-3, 2nd Ed. (2001-12-10)
|
|
*
|
|
*)
|
|
|
|
FUNCTION_BLOCK PID
|
|
VAR_INPUT
|
|
AUTO : BOOL ; (* 0 - manual , 1 - automatic *)
|
|
PV : REAL ; (* Process variable *)
|
|
SP : REAL ; (* Set point *)
|
|
X0 : REAL ; (* Manual output adjustment - *)
|
|
(* Typically from transfer station *)
|
|
KP : REAL ; (* Proportionality constant *)
|
|
TR : REAL ; (* Reset time *)
|
|
TD : REAL ; (* Derivative time constant *)
|
|
CYCLE : TIME ; (* Sampling period *)
|
|
END_VAR
|
|
VAR_OUTPUT XOUT : REAL; END_VAR
|
|
VAR ERROR : REAL ; (* PV - SP *)
|
|
ITERM : INTEGRAL ; (* FB for integral term *)
|
|
DTERM : DERIVATIVE ; (* FB for derivative term *)
|
|
END_VAR
|
|
ERROR := PV - SP ;
|
|
(*** Adjust ITERM so that XOUT := X0 when AUTO = 0 ***)
|
|
ITERM (RUN := AUTO, R1 := NOT AUTO, XIN := ERROR,
|
|
X0 := TR * (X0 - ERROR), CYCLE := CYCLE) ;
|
|
DTERM (RUN := AUTO, XIN := ERROR, CYCLE := CYCLE) ;
|
|
XOUT := KP * (ERROR + ITERM.XOUT/TR + DTERM.XOUT*TD) ;
|
|
END_FUNCTION_BLOCK
|
|
|